Skip to content

SBW Series Temperature Transmitter

The SBW series thermocouple and thermal resistor temperature transmitters are field-mounted temperature-transmitter units used with industrial thermocouples and RTDs. They use a two-wire transmission mode to convert industrial thermocouple and thermal-resistor signals into linear 4 to 20 mA or 0 to 10 mA output signals. The transmitter can be directly installed in the junction box of a thermocouple or RTD to form an integrated structure.

  • Temperature-signal conversion with industrial thermocouples and RTDs.
  • Installation in thermocouple or RTD junction boxes, or as a functional module in testing equipment and instrument panels.
  • Applicable sectors include metallurgy, petroleum, chemical industry, electric power, light industry, textile, food, national defense and scientific research among the applicable industrial sectors.
  • Silicone or epoxy-resin sealed construction is shock-resistant and moisture-resistant for harsh site environments.
  • Direct 4 to 20 mA or 0 to 10 mA output in a sensor junction box improves anti-interference performance during long-distance signal transmission.
  • Thermocouple transmitters provide cold-end temperature automatic compensation.
  • Isolated type available, with 0.5 kV isolation voltage between input and output.
  • Intelligent type supports remote information management, configuration, variable monitoring, calibration and maintenance through a HART protocol, handheld device or PC.
  • Intelligent type can adjust the display direction and display medium temperature, changes in sensor value, output current and percentage.
  • Conventional type: used as a field module.
  • Guide rail type: installed on a guide rail.
  • Can be directly installed in the junction box of a thermocouple or RTD.
  • Wiring arrangements are available for the intelligent and HART temperature modules.
Item Parameter
Input signal Thermocouple: K, E, J, B, S, T, N; thermal resistance: Pt100, Cu100, Cu50 (three-wire system, four-wire system)
Intelligent-type input setting Can be set arbitrarily by PC or handheld device
Output signal 4 to 20 mA DC within the range; linear with thermocouple/thermal-resistor input signal or temperature
HART-type output 4 to 20 mA DC signal simultaneously superimposed with HART standard protocol communication signals
Basic error Intelligent: 0.2%FS / 0.5%FS; HART type: 0.1%FS
Wiring method Two-wire system, three-wire system, four-wire system
Display mode Four-digit LCD displays field temperature; intelligent four-digit LCD can display field temperature, sensor value, output current or percentage ratio
Working voltage Intelligent type: 8 to 36 V; HART type: 12 to 30 V; rated working voltage: 24 V
Load resistance 600 Ω (24 V DC power supply)
Item Parameter
Ambient temperature (smart) 20 to 80°C
Ambient temperature (HART) -40 to 85°C
Ambient temperature (digital display type) 20 to 80°C
Relative humidity <85%RH
Temperature drift <50 ppm/°C
Operating environment No corrosive gas or similar environment
Temperature influence coefficient δ<0.05%/°C
Category Material Graduation Measuring range
Thermocouple Nichrome-Constantan E Optional within 0 to 800°C
Thermocouple Nichrome-Nickel-Silicon K Optional within 0 to 1300°C
Thermocouple Nichrome-Silicon-Nickel-Silicon N Optional within 0 to 1300°C
Thermocouple Platinum-Rhodium 10-Platinum-Rhodium S Optional within 0 to 1600°C
Thermocouple Platinum-Rhodium 30-Platinum-Rhodium 6 B Optional within 600 to 1800°C
Thermocouple Copper-Constantan T Optional within 0 to 400°C
Thermocouple Iron-Constantan J Optional within 0 to 800°C
Thermal resistor Copper Thermal Resistor Cu50 Optional within -50 to 150°C
Thermal resistor Copper Thermal Resistor Cu100 Optional within -50 to 150°C
Thermal resistor Platinum Thermal Resistor Pt100 Optional within 200 to 800°C
Item Options
Category code R: Thermocouple; Z: Thermal Resistor
Sensor code 1: Adapted K thermocouple/Pt100 thermistor; 2: Adapted E thermocouple/Cu100 thermistor; 3: Adapted J thermocouple/Cu50 thermistor; 4: Adapted B thermocouple; 5: Adapted S thermocouple; 6: Adapted T thermocouple; 7: Adapted N thermocouple; 9: Custom by user
Circuit category 0: Isolated type; 1: Non-isolated type
Installation method 0: Conventional type; 1: Guide rail type
Type of transmitter 0: Conventional type; 1: Isolated type; 2: Digital display type; 3: HART Protocol type; 4: Self-power; 5: Other types
  • SBW-R: thermocouple temperature transmitter.
  • SBW-Z: thermal-resistor temperature transmitter.
  • The specific model is determined by the sensor, circuit category, installation method and transmitter-type codes.
  • Input sensor category, graduation, measuring range and wiring method.
  • Required output signal, supply voltage, load resistance and isolation requirement.
  • Conventional- or guide-rail-mounting requirement, and whether installation in a sensor junction box is required.
  • Requirement for digital display, HART protocol, intelligent setting or self-power function.
  • Site ambient temperature, humidity, corrosive-gas conditions and quantity.
  • Industrial thermocouples and RTDs: the SBW series is used with these sensors and can be directly installed in their junction boxes.