Control Cable with XLPE Insulation

This control cable with XLPE insulation is designed for AC control, monitoring and protection circuits rated up to 450/750V. Copper braid, copper tape or aluminium-plastic composite tape shielding can be selected, together with steel tape or steel wire armour for mechanical protection.

  • Industrial equipment control, monitoring and protection circuits.
  • Fixed installation indoors, in cable trenches and conduits.
  • Control systems requiring shielding, flexibility, armour or low-smoke halogen-free sheaths.
  • Long-term conductor operating temperature: 90℃.
  • Installation temperature: not lower than 0℃.
  • Minimum bending radius: 8D for unarmoured cables and 12D for armoured or copper-tape-shielded cables.
  • PVC, PE and polyolefin outer sheaths are available.
Item Specification
Standard GB/T 9330-2020
Rated voltage 450/750V
Conductor Copper
Common cross-sections 0.5, 0.75, 1.0, 1.5, 2.5, 4, 6 and 10mm²
Core options 2-61 cores, depending on type and cross-section
Type Construction
KYJV, KYJY XLPE insulation with PVC or PE sheath
KYJVP Copper wire braided shielding
KYJVP2 Copper tape shielding
KYJVP3, KYJYP3 Aluminium-plastic composite tape shielding
KYJV22, KYJY23 Steel tape armour
KYJV32, KYJY33 Steel wire armour
  • DC conductor resistance at 20℃ complies with GB/T 3956.
  • Power-frequency AC withstand test: 3.0kV for 5min without insulation breakdown.
  • Insulation resistance at 70℃ meets the applicable type and cross-section requirements.