This RS485 communication cable is designed for Modbus RTU serial communication between DCS, SIS, PLC, CCS, MMS and other systems. Balanced transmission and differential reception support long-distance, multipoint half-duplex communication in industrial and building automation networks.

  • Modbus RTU communication between DCS, PLC, SIS, CCS and MMS systems.
  • Industrial and building automation control networks.
  • Field links from tens of metres to several kilometres requiring common-mode noise suppression.
  • Rated voltage: 300/500V; long-term conductor temperature: 70℃.
  • Transmission speed: 10Mbps with half-duplex operation.
  • Balanced transmission and differential reception help suppress common-mode interference and detect signals as low as 200mV.
  • Metal-tape shielding, metal-wire shielding and steel-tape or steel-wire armour are available.
  • Long-term bending radius: no more than 12D for metal-tape-shielded or armoured cables and 8D for metal-wire braided cables.
Item Specification
Standards IEC 61158-2-2010, T/HGJ 12400-2021 and T/CES 100-2022
Operating capacitance at 1kHz Core-to-core ≤85pF/m; core-to-shield ≤115pF/m for 0.5-1.0mm² or ≤125pF/m for 1.5mm²
Capacitance unbalance to earth ≤500pF/km
Characteristic impedance at 31.25kHz 100±20Ω
Attenuation ≤3.0dB/km at 39kHz; ≤0.5dB/km at 1kHz for 22AWG
AC withstand test 1kV/1min
Insulation resistance At least 3000MΩ·km at 20℃
Propagation delay difference ≤1.7μs/km at 7.8-39kHz

P/P1/P3/P4 indicate shielding methods, 2/3/9 indicate steel-tape, steel-wire or steel-wire-braided armour, V/Y indicate PVC or PE/polyolefin sheath and R indicates flexible construction.